More info
Name: HIGH VOLTAGE INSULATION TESTER 500/1000/2500/5000V
Functions
- Wide range measurements from 500V to 5000V and up to 1000GO.
- Large digital display with Bar Graph indication and back light.
- Polarization Index measurement (PI).
- Timer measurement function.
- Indication of Output voltage and Discharge voltage.
- Auto-discharge function and Voltage output warning function.
- Auto power off and Battery Check.
- Safety standard IEC 61010-1 CAT III 600V
_____________________________________
Range Insulation resistance Voltage
measurement
500V 1000V 2500V 5000V AC/DC V
Measuring range 0.0 - 99.9MO
100 - 999MO 0.0 - 99.9MO
100 - 999MO
1.00 - 1.99GO 0.0 - 99.9MO
100 - 999MO
1.00 - 9.99GO
10.0 - 99.9GO 0.0 - 99.9MO
100 - 999MO
1.00 - 9.99GO
10.0 - 99.9GO
100 - 1000GO
(1TO) 30 - 600V
AC/DC
[50/60Hz]
Accuracy |±5%rdg |±3dgt |±5%rdg |±3dgt |±5%rdg |±3dgt |±5%rdg |±3dgt
|±20%(100GO or more) |±2%rdg |±3dgt
Short Circuit Current 1.3mA approx. -------
Rated test Current 1mA to 1.2mA
at 0.5MO load 1mA to 1.2mA
at 1MO load 1mA to 1.2mA
at 2.5MO load 1mA to 1.2mA
at 5MO load -------
Open circuit voltage 500VDC
+30%
-0%
1000VDC
+20%
-0%
2500VDC
+20%
-0%
5000VDC
+20%
-0%
-------
Maximum display 999 Counts (1000 counts only at 1000GO) 630 Counts
Current consumption About 1000mA (During measurement) 110mA approx.
Withstand Voltage
Safety standard 5320V AC for 5 seconds
IEC 61010-1 CAT III 600V, pollution Degree 2
Power supply DC12V : R14×8
Dimensions 205(L) × 152(W) × 94(D)mm
Weight 1.8kg approx.
Accessories 7165A (Line probe)
7224A (Earth cord)
7225A (Guard cord)
8019 (Hook type prod)
9159 (Carrying case [Hard])
LR14×8pcs (Alkaline battery size)
Instruction Manual
Optional 7168A (Line probe with alligator clip)
7253 (Longer Line probe with alligator clip)
8302 (Adaptor for recorder)