More info
Name: LEAKAGE CLAMP METER 2432
Functions
- High Sensitive Model
- Frequency Selector Switch to eliminate the effect of harmonics.
- Three AC current ranges : 4mA/40mA/100A
_____________________________________
AC A
(50/60Hz) 4/40mA/100A
|±1%rdg±5dgt (4/40mA)
|±1%rdg±5dgt (0 - 80A)
|±5%rdg (80.1 - 100A)
AC A
(WIDE) 4/40mA/100A
|±1%rdg±5dgt [50/60Hz],
|±2.5%rdg±10dgt [20Hz - 1kHz] (4/40mA)
|±1%rdg±5dgt [50/60Hz],
|±2.5%rdg±10dgt [40Hz - 1kHz] (0 - 80A)
|±5%rdg [50/60Hz],
|±10%rdg [40Hz - 1kHz] (80.1 - 100A)
Frequency Response 20Hz - 1kHz (40Hz - 1kHz:100A)
Maximum
Circuit Voltage 600V AC/DC (between line/neutral)
300V AC/DC (against earth)
Conductor Size Ø40mm max.
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-032
Effect of External
Stray Magnetic Field 2mA AC approx. in proximity to a 15mm-dia
conductor carrying 100A AC
Withstand Voltage 3700V AC for 1 minute
Response Time Approx. 2 seconds
Power Source Two R03 or equivalent (DC1.5V) batteries
Dimensions 185(L) × 81(W) × 32(D)mm
Weight 290g approx.
Accessories 9052 (Carrying Case)
R03 (1.5V) × 2
Instruction Manual
Optional 8008 (Multi-Tran)*
* This Multi-Tran can not be used for leakage current measurement