More info
Name: DIGITAL INSULATION / CONTINUITY TESTER 3007A
Functions
- Bargraph to display insulation resistance.
- Displays the value of external AC voltage along with flashing symbol.
- Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
-Trac-Lok mode to conserve battery life on insulation and continuity tests.
- Live circuit warning beeper.
- Releasing the test button automatically discharges the charges stored in the circuit under test.
-Backlight function to view the test results in dimly lit areas.
- 200mA continuity measuring current to IEC 61557.
- Minimum 1mA current on insulation tests to IEC 61557.
_____________________________________________
Insulation Resistance
Test Voltage 250V/500V/1000V
Measuring Ranges
(Mid-scale Value) 20MO/200MO/2000MO
Output Voltage
on open circuit Rated test voltage+20%, -0%
Nominal Current 1mA DC min.
Output Short
Circuit Current 1.5 mA DC approx.
Accuracy |±1.5%rdg±5dgt (20MO/200MO)
|±10%rdg±3dgt (2000MO)
Continuity Test
Measuring Ranges
(Mid-scale Value) 20O/200O/2000O
Output Voltage
on open circuit 7 - 12V DC
Measuring Current 200mA DC min.
Accuracy |±1.5%rdg±5dgt (20O)
|±1.5%rdg±3dgt (200O/2000O)
AC Voltage
AC Voltage range 0-600V AC
Accuracy |±5%rdg±3dgt
General
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-031 IEC 61557-1/2/4
IP Rating IEC 60529-IP54
EMC Standard IEC 61326-1
Withstand Voltage 3700V AC for 1 minute
Power Source R6 (AA) (1.5V) × 8
Dimensions 185(L) × 167(W) × 89(D)mm
Weight 990g approx
Accessories 7122B (Test leads) Pouch for test leads
8923 (F500mA/600V fuse) × 2
R6 (AA) × 8
Shoulder Strap
Instruction Manual